OGNEZA-PM (TK) fire collar for floor drains and roof outlets
Fire collar for plastic pipes of floor drains and roof outlets in floor slabs: EI 90 for drain systems, EI 180 for roof outlets.

OGNEZA-GT is a one-component grey acrylic paste that expands when heated from approximately 200 °C. It is used to seal cable penetrations, joints in walls and floors, and expansion joints between concrete elements inside fire-hazardous premises. Fire resistance is up to 150 minutes; certificates under TR EAEU 043/2017 are issued for 60 and 150 minutes. Movement capability is ±20 %, the operating range is from −40 to +120 °C, and the service life is at least 10 years. Voids in the opening are filled with mineral wool.
| Manufacturer | OGNEZA — OOO “OGNEZA”, St Petersburg |
|---|---|
| Fire protection performance | up to 150 min; certificates under TR 043: 60, 150 min; GT(L) — 60, 150, 180 min; sleeve — 60 and 150 min |
| Application | cable lines, penetrations and joints, concrete and reinforced concrete |
| Service conditions | inside fire-hazardous premises: cable penetrations, joints in walls/floors, expansion joints between concrete elements; service temperature from −40 to +120 °C |
| Base | acrylic one-component paste, expands from ~200 °C |
| Colour | grey |
| Packaging | 310 ml cartridge (400 g), 3 kg bucket, 20 kg bucket; cartridges — in a box ≤ 6.8 kg |
| Application method | gun, brush, spatula; voids — mineral wool |
| Application temperature | from +5 to +40 °C |
| Drying | 3 mm — 24 h, 1 mm — 8 h |
| Shelf life | 12 months |
| Standards | TU 2313-004-92450604-2013; certificates under TR EAEU 043/2017; state registration certificate |
Data from the manufacturer’s technical data sheet. The coating system, number of coats and quantity are selected for your project on request.
Fire collar for plastic pipes of floor drains and roof outlets in floor slabs: EI 90 for drain systems, EI 180 for roof outlets.
Water-based intumescent paint for fire protection of steel structures indoors: 15–90 minutes, groups 7–3 per GOST R 53295.
Extended collar with two intumescent inserts for plastic pipes in floors; fire resistance rating 180 minutes.
Self-priming fire-retardant varnish for timber, including parquet and facades: groups I and II, G1, V1, D2, T2, RP1, UV resistance.
Acrylic highly elastic fire-stopping sealant for expansion joints and pipe penetrations; up to EI 240, operates from −60 to +120 °C.
Self-adhesive intumescent tape for fire doors, hatches, dampers and air duct flanges; up to EI 240 as part of an assembly.