Framed fire protection cable enclosure of non-combustible KNAUF-Fireboard boards
Framed enclosure of KNAUF-Fireboard boards keeps cable lines operational in a fire for 45–150 minutes, with AQUAPANEL up to 180.

The frameless cable enclosure is assembled from KNAUF-Fireboard boards joined with KNAUF Z-cnk construction staples or self-tapping screws, in sections up to 2,000 mm long. Dispensing with the framework simplifies installation and makes the system cheaper, and the lid can be left loose-laid for cable maintenance. In a fire, the cables inside the enclosure remain operational for 45–150 minutes (GOST R 53316); if necessary, an AQUAPANEL layer is added on the outside. Installation and service conditions: premises or canopies, temperature not below +5 °C, humidity up to 75 %, without moisture or precipitation; service life at least 25 years.
| Manufacturer | KNAUF — OOO KNAUF GIPS, made in Russia |
|---|---|
| Fire protection performance | cable line circuit integrity 45–150 min (GOST R 53316) |
| Application | cable lines |
| Service conditions | indoors or under a canopy, t not below +5 °C, humidity not above 75 %, without moisture or precipitation |
| Base | KNAUF-Fireboard boards 20/24 mm, joined with KNAUF Z-cnk construction staples or self-tapping screws; optionally AQUAPANEL 8/12.5 mm |
| Application method | frameless installation in sections up to 2,000 mm; the lid can be loose-laid for maintenance |
| Application temperature | installation at t not below +5 °C and humidity not above 75 % |
| Standards | GOST R 53316; technical regulation KS 26.07/2021 |
Data from the manufacturer’s technical data sheet. The coating system, number of coats and quantity are selected for your project on request.
Framed enclosure of KNAUF-Fireboard boards keeps cable lines operational in a fire for 45–150 minutes, with AQUAPANEL up to 180.
Frameless enclosure of KNAUF-Fireboard boards around rectangular and circular steel air ducts and smoke exhaust systems.
Framed cladding of steel structures with KNAUF-Fireboard boards: fire protection performance groups 1–7, up to R 240.
Non-combustible NG gypsum board with vermiculite and glass roving for fire protection cladding of steel, cable enclosures and air ducts.
Frameless cladding of steel structures with KNAUF-Fireboard boards: fire protection performance groups 1–7, up to R 240.