TERMOBARIER fire protection paint (solvent-borne)
Thin-film intumescent paint on modified acrylic for steel structures inside buildings, R15–R90, application down to −20 °C.

On open industrial sites, steel structures are protected with TERMOBARIER 2 epoxy compound. The two-component material with an amine hardener contains no solvent, is resistant to petroleum products and serves in the UKhL1 climate from −60 to +60 °C and at 100 % humidity, even without a finishing coat. Fire protection performance is from R15 to R90; the compound can be applied directly to steel without a primer, using airless piston units only. The kit consists of 20 kg of component A and 5 kg of component B in metal euro pails.
| Manufacturer | TERMOBARIER — OOO NPK OgneKhimZashchita, Saint Petersburg |
|---|---|
| Fire protection performance | R15, R30, R45, R60, R90 (fire protection performance groups 7 to 3 to GOST R 53295-2009) |
| Application | steel structures |
| Service conditions | open industrial atmosphere UKhL1 and indoors, from −60 °C to +60 °C (briefly up to +100 °C), humidity up to 100 %, including without a finishing coat; resistant to petroleum products |
| Base | two-component compound on epoxy resins with an amine hardener, solvent-free (solids content at least 97 %) |
| Colour | dark grey to black |
| Packaging | metal euro pail 20 kg + 5 kg (components A + B) |
| Application method | airless spray only (piston units); solvents and water not permitted |
| Application temperature | from 0 °C to +35 °C (from −10 °C: special supply); humidity up to 90 %; no precipitation; surface 3 °C above dew point |
| Drying | pot life of the mix at least 1 h (+20 °C) / 2 h (0 °C); before finish 2 / 7 days; development of properties and hardness 2 / 5 months |
| Compatible primers and topcoats | primer not mandatory (can be applied directly to steel); systems: GF-021; SILMAKS Zinc; SILMAKS Zinc + SILMAKS AS; finish if required: polyurethane, acrylic, epoxy |
| Shelf life | 12 months from the date of manufacture; storage from −60 °C to +45 °C |
| Standards | TU 20.30.22-007-30642285-2017; GOST R 53295-2009; TR EAEU 043/2017 (EAEU certificate RU C-RU.PB09.V.00612/26); 123-FZ; SP 14.13330.2014 |
Data from the manufacturer’s technical data sheet. The coating system, number of coats and quantity are selected for your project on request.
Thin-film intumescent paint on modified acrylic for steel structures inside buildings, R15–R90, application down to −20 °C.
Weather-resistant two-layer epoxy system for fire protection of steel outdoors and indoors, up to R150 (group 1).
Two-layer fire protection system for steel structures inside buildings: TERMOBARIER T insulating layer and TERMOBARIER paint, up to R150.