TERMOBARIER fire protection paint (solvent-borne)
Thin-film intumescent paint on modified acrylic for steel structures inside buildings, R15–R90, application down to −20 °C.

TERMOBARIER K raises the fire protection of steel structures to R150 (group 1) by means of two layers: first the TERMOBARIER T thermal insulation material, two-component and solvent-free, is sprayed, then the TERMOBARIER intumescent paint. The system is intended for indoor use only: from −45 to +45 °C, humidity up to 90 %, without condensation or aggressive environments. A VNIIPO MChS of Russia conclusion on compliance with SP 2.13130.2020 has been obtained; seismic resistance is up to 9 points on the MSK-64 scale. Both layers are applied by airless spray.
| Manufacturer | TERMOBARIER — OOO NPK OgneKhimZashchita, Saint Petersburg |
|---|---|
| Fire protection performance | up to R150 (fire protection performance group 1 to GOST R 53295-2009) |
| Application | steel structures |
| Service conditions | indoors only, from −45 °C to +45 °C (briefly up to +80 °C), humidity up to 90 % without condensation or aggressive environments |
| Colour | TERMOBARIER T: light green; paint: white/light grey |
| Application temperature | TERMOBARIER T: from 0 °C to +35 °C (from −10 °C: special supply); paint: from −20 °C to +35 °C; humidity up to 90 % |
| Drying | before applying the paint: 2 / 7 days |
| Compatible primers and topcoats | epoxy, polyurethane, alkyd primers (GF-021 or SILMAKS Zinc); finish: alkyd, polyurethane, acrylic (SILMAKS AS) |
| Shelf life | 12 months from the date of manufacture |
| Standards | TU 5768-005-30642285-2016; TU 2313-001-30642285-2011; GOST R 53295-2009; SP 2.13130.2020; TR EAEU 043/2017 (EAEU certificate RU C-RU.PB09.V.00605/26) |
Data from the manufacturer’s technical data sheet. The coating system, number of coats and quantity are selected for your project on request.
Thin-film intumescent paint on modified acrylic for steel structures inside buildings, R15–R90, application down to −20 °C.
Weather-resistant two-layer epoxy system for fire protection of steel outdoors and indoors, up to R150 (group 1).
Two-component solvent-free epoxy fire protection compound for steel outdoors, R15–R90, 20 + 5 kg kit.