Attik (fire and bio-protective impregnation) for timber (KrilaK)
Colourless fire and bio-protective impregnation for timber indoors, fire protection performance group I with two coats per NPB 251-98.
Monolit OM is mineral fire protection specifically for metal: a dry mix of hydraulic binder with fillers, which is mixed with water. Fire protection performance per GOST R 53295 is up to 240 min. The coating is used indoors and in the open atmosphere in the UKhL version, with service temperatures from −60 to +45 °C. It is applied mechanically (Putzmeister P11, MIS-800, T-103 and equivalents) or by spatula at temperatures not below +5 °C; coating formation takes 28 days.
| Manufacturer | KrilaK — NPO “Association KrilaK” |
|---|---|
| Fire protection performance | fire protection performance up to 240 min per GOST R 53295 |
| Application | steel structures |
| Service conditions | indoors and in the open atmosphere, UKhL; from −60 to +45 °C |
| Base | dry mix of hydraulic binder with fillers; mixed with water 1:1 |
| Colour | grey |
| Packaging | 25 kg bags, on pallets |
| Application method | mechanically (Putzmeister P11, ISO-P5, CAFCO MIX, CAFCO JET, MIS-800, T-103 and equivalents), spatula; mesh reinforcement for layers > 12 mm |
| Application temperature | not below +5 °C, relative humidity ≤ 95 % |
| Drying | between coats 2–6 h; coating formation 28 days |
| Compatible primers and topcoats | primers Akrilak EP Primer, Akritsink Protect; decorative Akrilak Finish, Akrilak ARM (RAL) |
| Shelf life | storage in dry enclosed premises |
| Standards | TU 23.64.10-107-42443059-2019; GOST R 53295; 123-FZ |
Data from the manufacturer’s technical data sheet. The coating system, number of coats and quantity are selected for your project on request.
Colourless fire and bio-protective impregnation for timber indoors, fire protection performance group I with two coats per NPB 251-98.
Mineral fire-protective mix for steel structures, R up to 240, group 1 per NPB 236-97, including hydrocarbon fire.
Fire-protective cable coating for 100 % humidity and precipitation at NPPs, chemical plants and in the fuel and energy sector; RP1, D1, V1, T1.
Two-component epoxy coating for steel structures, fire protection performance group 1 per GOST R 53295-2009 (up to 180 minutes).
Dry mix from which Joker M water-based fire-retardant paint for steel structures with a fire resistance rating of R up to 90 is prepared on site.
Sprayable mineral mix for fire protection of steel structures, R up to 240 including hydrocarbon fire, for unheated structures.