OGRAX-OTP fire protection pillows
Fibreglass fabric pillows with intumescent filler for cable penetrations and fire barrier belts; fire resistance up to 120 minutes.

At open industrial sites with aggressive environments, steel and concrete are protected with OGRAX-NSh-A plaster. The low-density dry mix is mixed with water and applied by wet shotcreting or with plastering stations over primer. The material is non-combustible and weather-resistant and works from −50 to +60 °C; fire protection is up to 240 minutes, and service under hydrocarbon fire conditions is possible. The coating is lightweight, with a service life of at least 25 years.
| Manufacturer | OGRAX — GK Unihimtek, Moscow Region |
|---|---|
| Fire protection performance | up to 240 minutes; the table gives 150 and 180 min; service under hydrocarbon fire conditions is possible |
| Application | steel structures, concrete and reinforced concrete |
| Service conditions | industrial (open) atmosphere, from −50 to +60 °C |
| Base | low-density non-combustible plaster mix, mixed with water; bulk density 320±25 kg/m³ |
| Colour | light grey, beige-grey |
| Packaging | multi-layer paper or polypropylene bags with a liner |
| Application method | wet shotcreting in layers or plastering stations; over primer |
| Application temperature | from +5 to +30 °C, RH 50–85% |
| Drying | between coats 12 h, full drying 20–30 days |
| Shelf life | 1 year |
| Standards | TU 23.99.19-093-13267785-2023; GOST R 53295-2009; TR EAEU 043/2017 |
Data from the manufacturer’s technical data sheet. The coating system, number of coats and quantity are selected for your project on request.
Fibreglass fabric pillows with intumescent filler for cable penetrations and fire barrier belts; fire resistance up to 120 minutes.
Water-based intumescent coating for cables with PE, PVC and rubber sheaths in enclosed premises; complies with GOST R 53311-2009.
Extruded tape of oxidised graphite and PVC with an adhesive transfer layer; 90 minutes of protection against the passage of gases, flame and smoke.
Two-component epoxy fire protection for steel in the open atmosphere and extremely aggressive environments, R45–R120, hydrocarbon fire.
Two-component spray polyurethane foam for structural fire and cryogenic protection of steel structures; ratings of 60, 90, 120 and 150 minutes.
Split steel collars with an intumescent insert for plastic sewer and water supply pipes; EI 180, diameters 16–110.