OGRAX-VV fire protection coating for cables (moisture-resistant)
Moisture-resistant water-based coating for fire protection of category A and B cables in cable structures and outdoors; GOST R 53311-2009.

OGRAX-LTU differs from OGRAX-L tape in its technology: it is an extruded material based on oxidised graphite and PVC with adhesive transfer tape, with a smooth or ribbed surface. Intumescence starts at +180 °C; for 90 minutes the tape prevents the passage of gases, flame and smoke. Applications include fire doors, partitions, dampers, air duct flanges, lift shafts, safes, collars and reinforced concrete fire-rated structures. The operating range is from −60 to +60 °C at humidity up to 100%.
| Manufacturer | OGRAX — GK Unihimtek, Moscow Region |
|---|---|
| Fire protection performance | prevents the passage of gases, flame and smoke for 90 minutes |
| Application | air ducts, fabrics, roofing and other materials |
| Service conditions | fire doors, partitions, dampers, air duct flanges, lift shafts, safes, collars, reinforced concrete fire-rated structures; from −60 to +60 °C, humidity up to 100% |
| Base | extruded material based on oxidised graphite and PVC with adhesive transfer tape; smooth and ribbed surface |
| Colour | from dark grey to black |
| Packaging | rolls of 10 m; width 8–500 mm; cardboard boxes |
| Application method | glue or mechanical fixing |
| Compatible primers and topcoats | can be painted over and covered with wallpaper |
| Shelf life | 1 year |
| Standards | TU 2.21.42-073-13267785-2019 |
Data from the manufacturer’s technical data sheet. The coating system, number of coats and quantity are selected for your project on request.
Moisture-resistant water-based coating for fire protection of category A and B cables in cable structures and outdoors; GOST R 53311-2009.
Non-combustible low-density plaster mix for fire protection of steel structures indoors, up to 240 minutes.
Two-component coating on a hybrid binder for fire protection of class A and H bulkheads and decks on ships and offshore platforms.
Weather-resistant solvent-based coating for fire protection of cables, including flood-prone ones; from −60 to +250 °C, GOST R 53311-2009.
Colourless water-based fire and bio-protection compound for timber structures indoors and outdoors; fire protection performance group 1.
Permanent cable penetration seal of mineral wool boards and OGRAX-VV compound for walls and floors; fire resistance up to 90 minutes.