TEKSOTERM polyacrylic fire-protective enamel for reinforced concrete structures
Intumescent polyacrylic coating for reinforced concrete, tunnels and ventilation shafts with fire resistance ratings REI 60, REI 90 and REI 150.

TEKSOTERM intumescent enamel gives steel structures a fire protection performance from 15 minutes (group 7) to 120 minutes (group 2). It is produced water-based (applied from +5 to +35 °C) and solvent-based (from −15 to +35 °C) and is applied by brush, roller or airless spraying. A primer is mandatory and its compatibility is agreed with the manufacturer; galvanised steel is painted without a primer. In premises with humidity up to 80 % the enamel works without a finish coat, while in damp premises, under a canopy and in the open atmosphere, including industrial and marine, it is overcoated with a finish coat.
| Manufacturer | TEKSOTERM — OOO “Yug-Tekhnologiya”, Rostov-on-Don |
|---|---|
| Fire protection performance | from 15 min (fire protection performance group 7) to 120 min (fire protection performance group 2) |
| Application | steel structures |
| Service conditions | indoors at humidity up to 80 % — without a finish coat; damp premises, under a canopy, open atmosphere, industrial and marine atmosphere — with a finish coat; coating service life 10–30 years depending on service conditions |
| Base | one-component polyacrylic intumescent enamel; produced water-based and solvent-based |
| Colour | matt white, uniform (slight orange peel acceptable) |
| Packaging | sealed factory metal containers |
| Application method | brush, roller, high-pressure airless spraying |
| Application temperature | water-based — from +5 to +35 °C; solvent-based — from −15 to +35 °C; relative humidity no more than 80 %; surface at least 3 °C above the dew point |
| Drying | before the finish coat — at least 48 h |
| Compatible primers and topcoats | priming is mandatory, primer compatibility is agreed with OOO “Yug-Tekhnologiya”; galvanised steel — no primer. Alkyd, alkyd-urethane, acrylic, epoxy, KhS primers; acrylic, alkyd, alkyd-urethane, vinyl-epoxy, alkyd-styrene, KhV, organosilicon, organosilicate, epoxy, polyurethane finishes — depending on service conditions |
| Shelf life | solvent-based — 12 months, water-based — 6 months; storage: water-based from +5 to +35 °C, solvent-based from −25 to +35 °C |
| Standards | enamel “TEKSOTERM-01”, TU 2316-008-14534633-2016 |
Data from the manufacturer’s technical data sheet. The coating system, number of coats and quantity are selected for your project on request.
Intumescent polyacrylic coating for reinforced concrete, tunnels and ventilation shafts with fire resistance ratings REI 60, REI 90 and REI 150.
Structural one-component compound on an acrylic binder for fire protection of steel structures, fire resistance rating 90, 120 and 150 minutes.
Intumescent polyacrylic enamel for metal ventilation and air-conditioning ducts and flue gas ducts: EI 30, EI 45, EI 60.