OGRAX-OTP fire protection pillows
Fibreglass fabric pillows with intumescent filler for cable penetrations and fire barrier belts; fire resistance up to 120 minutes.
OGRAX-NSh is the version of the non-combustible plaster for enclosed premises with humidity up to 85% and temperatures from −50 to +60 °C. It is used in civil and industrial construction for fire protection of steel structures with ratings of up to 240 minutes. The low-density dry mix is mixed with water and applied in layers by wet shotcreting or with a plastering station over primer at temperatures from +5 to +30 °C. Full drying takes 20–30 days; the colour is grey, and it is packed in multi-layer bags with a liner.
| Manufacturer | OGRAX — GK Unihimtek, Moscow Region |
|---|---|
| Fire protection performance | up to 240 minutes; the table gives R150 |
| Application | steel structures |
| Service conditions | enclosed premises with humidity up to 85%, from −50 to +60 °C |
| Base | low-density non-combustible plaster mix, mixed with water; bulk density 250±25 kg/m³ |
| Colour | grey |
| Packaging | multi-layer paper or polypropylene bags with a liner |
| Application method | wet shotcreting in layers or plastering stations; over primer |
| Application temperature | from +5 to +30 °C, RH 50–85% |
| Drying | between coats 12 h, full drying 20–30 days |
| Shelf life | 1 year |
| Standards | TU 5728-056-13267785-07; GOST R 53295-2009; TR EAEU 043/2017 |
Data from the manufacturer’s technical data sheet. The coating system, number of coats and quantity are selected for your project on request.
Fibreglass fabric pillows with intumescent filler for cable penetrations and fire barrier belts; fire resistance up to 120 minutes.
Split steel collars with an intumescent insert for plastic sewer and water supply pipes; EI 180, diameters 16–110.
Weather-resistant two-layer fire protection for steel, R90–R120: OGRAX-T thermal fire-insulating layer and OGRAX-MSK intumescent paint.
Two-component epoxy fire protection for steel in the open atmosphere and extremely aggressive environments, R45–R120, hydrocarbon fire.
Low-density non-combustible plaster for fire protection of steel and concrete in open industrial atmospheres, up to 240 minutes, hydrocarbon fire.
Two-component epoxy fire protection coating for steel in aggressive environments and marine climates, R45–R120, hydrocarbon fire.