OGRAX-M fire protection coating for cables
Weather-resistant solvent-based coating for fire protection of cables, including flood-prone ones; from −60 to +250 °C, GOST R 53311-2009.

For extremely aggressive environments, including marine climates and contact with oil and petrol, the range includes OGRAX-SKE, a two-component epoxy composition with fillers and a hardener. The coating works in the open atmosphere from −60 to +60 °C and provides fire resistance of steel from R45 to R120; service under hydrocarbon fire conditions is possible. It is applied by spray or trowel, with or without primer, including at sub-zero temperatures. Full cure takes 24 hours.
| Manufacturer | OGRAX — GK Unihimtek, Moscow Region |
|---|---|
| Fire protection performance | R45–R120; service under hydrocarbon fire conditions is possible |
| Application | steel structures |
| Service conditions | open atmosphere from −60 to +60 °C, including marine climate and aggressive media (oil, petrol) |
| Base | two-component: epoxy composition with fillers + hardener; solids content of component 1 — 93±3% |
| Colour | from grey to black |
| Packaging | metal containers with tight-fitting lids |
| Application method | combined or airless spray, trowel; mixing ratio 15:1 (up to +25 °C) or 20:1 (above +25 °C); pot life 2 h |
| Application temperature | permitted at sub-zero temperatures; RH ≤ 90% |
| Drying | between coats 4 h, full cure 24 h |
| Compatible primers and topcoats | applied with or without primer |
| Shelf life | 1 year |
| Standards | TU 5728-059-13267785-08; GOST R 53295-2009; TR EAEU 043/2017 |
Data from the manufacturer’s technical data sheet. The coating system, number of coats and quantity are selected for your project on request.
Weather-resistant solvent-based coating for fire protection of cables, including flood-prone ones; from −60 to +250 °C, GOST R 53311-2009.
Flexible intumescent roll material on fibreglass fabric for dry fire protection of cables, including armoured and flood-prone ones.
Permanent cable penetration seal of mineral wool boards and OGRAX-VV compound for walls and floors; fire resistance up to 90 minutes.