OGRAX-L1 roll-type fire protection for cables
Flexible intumescent roll material on fibreglass fabric for dry fire protection of cables, including armoured and flood-prone ones.

OGRAX-M has the widest temperature range among the OGRAX cable compounds: from −60 to +250 °C. The coating, made of a polymer with mineral fillers in an organic solvent, is weather-resistant, works at humidity up to 100% and is suitable for flood-prone cables. It can be applied from −25 °C; work is carried out with the voltage switched off and in compliance with the rules for handling flammable liquids. Compliance with GOST R 53311-2009 is confirmed by a TR EAEU 043/2017 certificate; the service life is at least 30 years.
| Manufacturer | OGRAX — GK Unihimtek, Moscow Region |
|---|---|
| Fire protection performance | complies with GOST R 53311-2009 (TR EAEU 043/2017 certificate) |
| Application | cable lines |
| Service conditions | high humidity (up to 100%) and outdoors, from −60 to +250 °C; including flood-prone cables |
| Base | polymer and mineral fillers in an organic solvent (solvent naphtha, R5, R6, ethyl acetate), weather-resistant |
| Colour | dark grey |
| Application method | airless spray in layers, roller, brush; work with the voltage switched off |
| Application temperature | from −25 to +50 °C, RH ≤ 95% |
| Drying | between coats at least 3 h, full 2–3 days |
| Shelf life | 1 year |
| Standards | TU 5728-070-13267785-11; GOST R 53311-2009; TR EAEU 043/2017 |
Data from the manufacturer’s technical data sheet. The coating system, number of coats and quantity are selected for your project on request.
Flexible intumescent roll material on fibreglass fabric for dry fire protection of cables, including armoured and flood-prone ones.
Non-combustible low-density plaster mix for fire protection of steel structures indoors, up to 240 minutes.
Permanent cable penetration seal of mineral wool boards and OGRAX-VV compound for walls and floors; fire resistance up to 90 minutes.
Two-component coating on a hybrid binder for fire protection of class A and H bulkheads and decks on ships and offshore platforms.
Two-component spray polyurethane foam for structural fire and cryogenic protection of steel structures; ratings of 60, 90, 120 and 150 minutes.
Intumescent tape on silica fabric for fire protection of plastic pipes inside walls and floors; EI 180.