Supply across Uzbekistan and to Kyrgyzstan, Tajikistan and Turkmenistan +998 93 815 00 53 Telegram sale@coatix.uz
PLAMCOR-6 thermal insulation layer for steel fire protection (VMP)
VMP

PLAMCOR-6 thermal insulation layer for steel fire protection (VMP)

On its own, PLAMCOR-6 is not a finished fire-protective coating. It is a two-component epoxy thermal insulation composition of the syntactic foam type: it is applied under the intumescent PLAMCOR-2, -3, -5, -302 or -303 to obtain combined structural fire protection. It suits all atmosphere types, including the open industrial atmosphere; service life of the system in the open atmosphere is at least 20 years. EAEU and NSOPB certificates and seismic resistance certificates are available.

Specifications

ManufacturerVMP — AO “NPKh VMP”, Yekaterinburg
Applicationsteel structures
Service conditionsmacroclimatic regions U, UKhL, KhL, all atmosphere types and placement categories per GOST 15150, incl. open industrial atmosphere
Baseepoxy thermal insulation composition (syntactic foam), two-component; volume solids 94±2 %
Colourlight pink (shade not standardised)
Packagingbase — 20 l metal bucket, hardener — 3 l
Application methodairless spray (nozzle ≥ 0.025″, ≥ 25 MPa, pump ≥ 57:1), trowel
Application temperaturefrom −5 to +30 °C, relative humidity ≤ 80 %; the material itself — not below +15 °C
Dryingto degree 3 — no more than 12 h; before overcoating with the intumescent layer — from 12 h to 3 weeks; full — at least 7 days (20 °C)
Compatible primers and topcoatsovercoated with intumescent PLAMCOR-2, -3, -5, -302, -303; primers TSINEP, IZOLEP-primer, IZOLEP-mastic, GF-021
Shelf life12 months
StandardsTU 20.30.22-121-12288779-2019; GOST 15150; GOST 9980.5; GOST 19007; GOST 31992.1; ASTM D 3359; EAEU, NSOPB certificates; seismic resistance certificates

Data from the manufacturer’s technical data sheet. The coating system, number of coats and quantity are selected for your project on request.