SPLEND-30 fire protection system for air ducts
EI30 fire protection system for air ducts: NATRSIL-S 541 adhesive compound and Folma-Kholst KhF foil-faced thermal insulation fabric.
The kaolin mastic is an aqueous suspension of a polymer binder and functional fillers that raises the fire resistance of steel structures up to R120. NEOFLAME 515 can be used even in premises without forced ventilation; it is sprayed with forced-feed units at temperatures from +5 °C. Besides fire protection, the compound serves as an adhesive for fixing thermal insulation materials to steel structures. It is used in premises with a non-aggressive environment and under a roofed canopy; in high humidity or in type II atmosphere a finishing enamel is applied over the mastic.
| Manufacturer | NEOFLAME (Teplokhim) — OOO NPP TEPLOKHIM, Dmitrov |
|---|---|
| Fire protection performance | up to R120 |
| Application | steel structures |
| Service conditions | indoors in a non-aggressive environment and under a roofed canopy; humidity not above 85 %, from −60 °C to +60 °C; U2 atm. II or high humidity: with a finish |
| Base | aqueous suspension of a polymer binder and functional fillers |
| Colour | white (can be tinted in pastel shades) |
| Application method | thick-film spraying with forced-feed units (Wagner HC 960/940 SSP); dilution with water up to 3 % |
| Application temperature | not below +5 °C; humidity not above 80 % |
| Drying | to degree 3: no more than 6 h |
| Compatible primers and topcoats | primers: alkyd, epoxy, alkyd-acrylic, phenolic, polyurethane, vinyl chloride (e.g. GF-021, AK-070); finish: PF-115, EP-1155D, KhP-7120, etc. |
| Shelf life | 12 months; storage from +1 °C to +40 °C (must not freeze) |
| Standards | TU 5760-051-66828143-2016 |
Data from the manufacturer’s technical data sheet. The coating system, number of coats and quantity are selected for your project on request.
EI30 fire protection system for air ducts: NATRSIL-S 541 adhesive compound and Folma-Kholst KhF foil-faced thermal insulation fabric.
Weather-resistant fire protection compound for steel up to R120 (cellulosic fire), works outdoors without a finishing enamel; 25 kg euro pail.
Thick-film sprayable compound with ablative fillers for structural fire protection of steel up to R150, application from −10 °C.
Water-based fire protection paint on polyvinyl acetate dispersion for steel structures in buildings, up to R90; 50 kg drum.
Two-component water-resistant compound for fire protection of cables in tunnels and flood-prone zones, withstands precipitation an hour after application.
EI90 fire protection system for air ducts: NATRSIL-S 541 compound and TEKh MAT KF foil-faced mineral wool mat.