VUP-2D fire protection paint for timber structures
Water-based fire protection paint for timber, fire protection performance group 1 to GOST R 53292; 50 kg drum.
NEOFLAME 513 is a water-based paint on a fine copolymer dispersion that protects steel structures up to R90. Besides steel, it is used to reduce the fire hazard of reinforced concrete blocks and panels, as well as composites: glass fibre and carbon fibre reinforced plastics and WPC. The coating is designed for residential, public and industrial buildings with a non-aggressive environment and for areas under a canopy at humidity not above 85 %; indoors the coating serves for 25 years, under a canopy for 10 years or more. It is applied by a high-pressure unit, brush or roller at temperatures from +5 °C.
| Manufacturer | NEOFLAME (Teplokhim) — OOO NPP TEPLOKHIM, Dmitrov |
|---|---|
| Fire protection performance | up to R90 (steel structures) |
| Application | steel structures, concrete and reinforced concrete, fabrics, roofing and other materials |
| Service conditions | inside residential, public and industrial buildings with a non-aggressive environment, outdoors under a canopy; humidity not above 85 %, from −60 °C to +60 °C |
| Base | water-based fine copolymer dispersion, fire retardants, fillers |
| Colour | white, tinting in pastel shades permitted |
| Packaging | polyethylene drum, 50 kg |
| Application method | high-pressure unit or manually by brush, roller; dilution with water up to 5 % |
| Application temperature | not below +5 °C; humidity not above 85 % |
| Drying | intercoat 3–6 h at +20 °C and humidity not above 85 % |
| Compatible primers and topcoats | primers: alkyd, acrylic, epoxy (including zinc-rich), phenolic, polyurethane, vinyl chloride |
| Shelf life | 12 months; storage and transport from +1 °C to +40 °C (must not freeze) |
| Standards | TU 2316-010-66828143-2016 |
Data from the manufacturer’s technical data sheet. The coating system, number of coats and quantity are selected for your project on request.
Water-based fire protection paint for timber, fire protection performance group 1 to GOST R 53292; 50 kg drum.
Water-based fire protection paint for cables and cable structures, complies with GOST R 53311 (flame damage length under 1.5 m).
Solvent-borne fire protection paint for steel structures up to R90, applied in frost down to −15 °C; 25 kg euro pail.
Water-emulsion intumescent paste for fire protection of steel structures inside buildings, up to R45; kit of paste and ammophos.
Water-based fire protection paint on polyvinyl acetate dispersion for steel structures in buildings, up to R90; 50 kg drum.
EI30 fire protection system for air ducts: NATRSIL-S 541 adhesive compound and Folma-Kholst KhF foil-faced thermal insulation fabric.